Indicator Status Meaning Diagnosis
Blinking yellow The memory riser
is waiting to
cancel the hot
swap operation.
To cancel the
operation, press
the memory riser
button again
within 5 seconds.
N/A
O The hot insertion
or removal
operation is
normal.
Memory riser
backup indicator
Steady green The memory riser
is idle.
N/A
O The memory riser
is not idle.
Memory riser
mirroring
indicator
Steady green Memory mirroring
has been
congured on the
memory riser.
N/A
O Memory mirroring
has not been
congured on the
memory riser.
Compute module
status indicator
Steady green The compute
module is
operating
properly.
N/A
Blinking red (once
every second)
The compute
module is faulty.
View the iBMC
event alarm logs
to check whether
the compute
module is faulty.
Blinking red (ve
times every
second)
The compute
module is not
installed properly.
Check whether
the compute
module is
installed properly.
O The compute
module is not
powered on.