EasyManua.ls Logo

Huawei FusionDC1000A - Replacing a Heat Detector (CE)

Huawei FusionDC1000A
180 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4.5.2 Replacing a Heat Detector (CE)
Prerequisites
A spare heat detector of the same model is available and functional.
Impact on the System
The re extinguishing system stops working during the replacement.
Preparations
Tools: protective gloves, step ladder, Phillips screwdriver
Materials: spare heat detector
Documents:
re extinguishing drawings and parameters
Skill requirement: re engineer
NO TICE
Before replacing the heat detector, inform the related administration department
of the temporary downtime of the re control system. After the replacement,
inform the administration department that the system has become operational.
Procedure
Step 1 Disconnect the battery cables, and switch o the input circuit breaker of the
extinguishant control panel.
Step 2 Hold the heat detector, and rotate it counterclockwise to remove it from the base.
Figure 4-96 Removing a heat detector
Step 3 Remove cables from the base.
FusionDC1000A Prefabricated All-in-One Data
Center
Maintenance Guide (IT Scenario) 4 Parts Replacement
Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd. 147