Device Method Check Standard Maintenance Guide
Smoke
detector
Check the smoke
detector indicator.
The indicator blinks
once every 6s.
Replace the smoke detector.
Heat
detector
Check the heat
detector indicator.
The indicator blinks
once every 6s.
Replace the heat detector.
SmartLi Operating
environment
There is no heat
source or direct
sunlight nearby.
Check that batteries are far away
from heat sources and are not
exposed to direct sunlight.
Appearance No damage, leakage,
or deformation is
found.
Disconnect the faulty battery
module, take photos, and replace
it with a new one..
Pressure gauge for
re detection and
re extinguishing
equipment
The pressure gauge
pointer is in the green
zone.
If the pressure gauge pointer is in
the red zone, contact Huawei
technical support.
3.4.6 Other Systems
Table 3-8 Monthly maintenance checklist for other systems
Item
Method Check Standard Troubleshooting
Pre-fab.
module
repainting
Check the pre-fab.
module exterior for
damage or corrosion.
The pre-fab. module and
bases are free from paint
ake-o, rust, or corrosion.
Maintain or replace the
rusty or damaged part of
the pre-fab. modules.
Repaint areas with paint
ake-o or rust.
External
environment
of pre-fab.
modules
Check whether
hazards or potential
hazards exist around
the pre-fab. modules.
No hazard or potential
hazard exists around the
pre-fab. modules.
Take measures to handle
potential hazards.
Check whether
obvious rubbish
exists around the
pre-fab. modules.
No obvious rubbish exists
around the pre-fab.
modules.
Clean the rubbish.
FusionDC1000A Prefabricated All-in-One Data
Center
Maintenance Guide (IT Scenario) 3 Routine Maintenance
Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd. 34