Device Method Check Standard Maintenance Guide
The pressure pointer of
the hand-held re
extinguisher is in the
green zone.
The re extinguisher is
within the validity
period.
SmartLi Battery module
appearance
The battery modules are
clean.
Clean the battery
modules using dry cotton
cloth. Exercise caution
when cleaning a battery
module because its
voltage is high.
Connections Each terminal is securely
connected.
Check the bolt at every
terminal. If any bolt is
loose, tighten it.
3.5.5 Other Systems
Table 3-13 Quarterly maintenance checklist for other systems
Item
Method Check Standard Troubleshooting
Ventilation
vent air lter
Check whether the
lter is blocked.
The air lter is
not blocked.
If an air lter is slightly blocked, clean
the air lter and reinstall it. If more
than 50% of the meshes are blocked,
replace the air lter.
Pre-fab.
module body
Check the pre-fab.
module.
The pre-fab.
module is clean.
1. Clean the pre-fab. module using a
long-handled soft brush and
alkaline or neutral detergent.
2. Wash the pre-fab. module with
clean water.
Pre-fab.
module
repainting
Check the pre-fab.
module exterior for
damage or corrosion.
The pre-fab.
module and
bases are free
from paint
ake-o, rust, or
corrosion.
Maintain or replace the rusty or
damaged part of the pre-fab. modules.
Repaint areas with paint ake-o or
rust.