4.1.2.1 Replacing an MDU
Prerequisites
Tools: Phillips screwdriver, key to the cabinet door
Materials: a new and intact MDU
NO TICE
The MDU can be replaced online without cutting o the power supply to
the SmartLi.
Before the replacement, ensure that the load services are not
aected or
obtain written consent from the customer.
Procedure
Step 1 Export the monitoring conguration of the SmartLi.
NO TE
If the MDU is damaged and the WebUI is still operational, you can export the MDU
conguration on the WebUI. Skip this step if both the MDU and WebUI are not operational.
Step 2 Remove the communications cable from the MDU and mark the connection
position
Step 3 Remove the four screws from the MDU using the Phillips screwdriver and set them
aside.
Step 4 Hold the MDU front panel by one hand, and push out the MDU from the fastener
on the front panel by the other hand.
Step 5 Install the new MDU and secure it.
Step 6 Reinstall the communications cable to the new MDU.
Step 7 Upload the software package and click Activate All.
Step 8 Set parameters.
Method 1: Power on the MDU, tap Settings on the home screen of the LCD,
and enter the initial password to log in. Tap System Settings and set
parameters as required.
Method 2: Import the conguration le. On the MDU home screen, choose
Maintenance > USB Operations and select Load Cong.
----End
4.1.2.2 Replacing a BCU
Prerequisites
Tools: Phillips screwdriver, key to the cabinet door
FusionDC1000A Prefabricated All-in-One Data
Center
Maintenance Guide (IT Scenario) 4 Parts Replacement
Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd. 52