Impact on the System
None
Preparations
Tool: multimeter
Material: spare light
Skill requirement: electrician's work permit
Procedure
Step 1 Locate a failed light.
If a light does not work but the cables to the light are intact, the light has
failed and needs to be replaced.
If all lights after a light do not work, the light adjacent to the working light
has failed.
Step 2 Disconnect the power supply to the lights.
Step 3 Remove the faulty light.
D ANGER
During replacement, do not touch any end of the light with bare hands. You will
get an electric shock if you touch bare electrodes.
Step 4 Install the new light in the original position.
----End
4.1.5 Replacing the Power PDB
Prerequisites
A spare power PDB of the same model is available and functional.
Impact on the System
None
Preparations
Tools: Phillips screwdriver, socket wrench
Material: spare power PDB
Documents: power supply and distribution drawings and parameters
Skill requirement: electrician's work permit
FusionDC1000A Prefabricated All-in-One Data
Center
Maintenance Guide (IT Scenario) 4 Parts Replacement
Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd. 56