Step 7 Remove the waterproof connector from the spare fan, as shown by (2) in Figure
Removing the fan and guard. Use a torque wrench to replace the hexagonal
waterproof connector delivered with the spare fan. The torque must be 3.75 N·m.
Step 8 Install the new fan in the sequence from Step 6 to Step 2.
Step 9 After re-power on, on the home screen of the indoor unit, choose Maint >
Diagnostic Mode > Enter, and set the outdoor unit speed to 100%. After the
outdoor unit has run for 5 minutes, check that the outdoor fan is running properly
and no alarm is raised.
Step 10 After
conrmation, set the outdoor unit speed to 0% and exit from the diagnostic
mode.
----End
4.2.2.6 Replacing the
Dierential Pressure Switch
Prerequisites
The
dierential pressure switch needs to be replaced.
A spare dierential pressure switch of the same model is available and
functional.
Tool: Phillips screwdriver
Context
The dierential pressure switch can be maintained only from the rear door.
Procedure
Step 1 On the controller home screen, tap Shutdown, and turn o the smart cooling
product switch in the upstream PDC.
NO TICE
Exercise caution because the device is still energized after it is shut down on the
controller home screen.
Step 2 Open the rear door and remove the air lter.
Step 3 Remove the pressure inlet tube, as shown by (1) in Figure 4-22.
FusionDC1000A Prefabricated All-in-One Data
Center
Maintenance Guide (IT Scenario) 4 Parts Replacement
Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd. 79