NO TE
For the diagrams, see the initial conguration parameter manual for the solution in use.
Procedure
Step 1 Switch on the input power circuit breaker of the re alarm control panel for the
protected area by referring to the power supply and distribution system diagram.
Step 2 Switch on the active and standby power supplies to power on the re alarm
control panel.
Figure 4-3 Positions of power switches
NO TE
If the power indicator is on and other indicators are
o, the power-on process succeeds. If a
yellow fault indicator is on, rectify the fault before continuing follow-up operations.
Step 3 Unlock the keyboard.
The keyboard is locked to prevent misoperation.
To unlock the keyboard, press Keyboard and then enter the password (the
initial password is 111111).
To lock the keyboard, press Keyboard when the keyboard is unlocked.
The keyboard will be locked if no operation is performed within 5 minutes.
Step 4 Set the time displayed on the
re alarm control panel.
Choose System Setting > Time Setting, enter the correct date and time, and click
OK. The system saves the time you have set.
----End
4.5.2 Commissioning the Emergency Light (Standard)
FusionDC1000A Prefabricated All-in-One Data
Center
Commissioning Guide (IT Scenario) 4 Commissioning Core Devices
Issue 02 (2022-12-15) Copyright © Huawei Digital Power Technologies Co., Ltd. 46