Item Specications
Number of detector loops Three loops. Loops 1 and 2 respectively connect
to smoke detectors and heat detectors. Loop 3
is reserved by default.
Number of detectors that can be connected to
a single loop
≤ 32
Wire system of the detector loop Two-wire system
Length of the detector loop ≤ 1000 m
Relay contact capacity 1 A/30 V DC for all relays
Output loop current limiting for the
electromagnetic valve
≥ 1 A
Output loop current limit for other drivers ≤ 1 A
7.2 Extinguishant Control Panel
The extinguishant control panel is the core of the gas extinguishing control
system. It receives signals from re detectors, processes alarm information, and
controls re extinguisher cylinders to release extinguishant.
Figure 7-5 Extinguishant control panel
7.3 Peruorohexanone Automatic Fire Extinguisher
When the FusionDC1000 catches re, a lot of smoke is generated and the
temperature rises sharply. The smoke detector and heat detector send re alarm
signals to the extinguishant control panel, which generates a voltage to start the
FusionDC1000A Prefabricated All-in-One Data
Center
Product Description (IT Scenario) 7 Fire Extinguishing System