2.3 Key Technical Specications
Table 2-3 Key technical specications
Conguration N+X-
Norma
l
Temp-
CE
N+X-
Low
Temp-
CE
2N-
Norma
l
Temp-
CE
2N-
Low
Temp-
CE
N+X-
Norma
l
Temp-
CCC
N+X
Low
Temp-
CCC
2N-
Norma
l
Temp-
CCC
2N-
Low
Temp-
CCC
General
specic
ations
Applicabl
e
temperat
ure range
–20°C
to
+55°C
–40°C
to
+45°C
–20°C
to
+55°C
–40°C
to
+45°C
–20°C
to
+55°C
–40°C
to
+45°C
–20°C
to
+55°C
–40°C
to
+45°C
Pre-fab.
module
dimensio
ns
(H x W x
D)
2896 mm x 2438 mm x 12,192 mm
Power
supply
and
distributi
on
architect
ure
N+X 2N N+X 2N
Total
power
54 kW. Derating is required when the temperature is greater than or equal
to 45°C.
Number
of
cabinets
8 6 8 6
Cabinet
specicati
ons (H x
W x D)
4 PCS: 2000 mm
x 600 mm x
1100 mm
4 PCS: 2000 mm
x 600 mm x
1200 mm
2 PCS: 2000 mm
x 600 mm x
1100 mm
4 PCS: 2000 mm
x 600 mm x
1200 mm
4 PCS: 2000 mm
x 600 mm x
1100 mm
4 PCS: 2000 mm
x 600 mm x
1200 mm
2 PCS: 2000 mm
x 600 mm x
1100 mm
4 PCS: 2000 mm
x 600 mm x
1200 mm
NOTE
1200 mm deep cabinet: A device with a depth of less than or equal to 750 mm can
be installed. You can move the mounting bar on the front door to install a device
with a depth of 850 mm.
1100 mm deep cabinet: A device with a depth of less than or equal to 750 mm can
be installed.
FusionDC1000A Prefabricated All-in-One Data