Loading...
Conguration N+X-
Norma
l
Temp-
CE
N+X-
Low
Temp-
CE
2N-
Norma
l
Temp-
CE
2N-
Low
Temp-
CE
N+X-
Norma
l
Temp-
CCC
N+X
Low
Temp-
CCC
2N-
Norma
l
Temp-
CCC
2N-
Low
Temp-
CCC
Video
surveillan
ce
Huawei high-denition IP camera
Video
storage
SD card (7-day storage), optional IVS (longer storage and advanced
management as required)
(Optional
) Mobile
O&M
Mobile O&M using mobile phones and PADs
E-mail
(optional
)
An email server can be congured.
NO TICE
Do not leave the prefabricated data center power o for a long time. If the
data center will be idle for a long time, power the lithium batteries on and
keep them operational for at least two hours every six months. Power the lead-
acid battery cabinets on and keep them operational for at least three hours
every three months.
The battery storage temperature must be in the range from 0°C to 40°C.
Batteries can be stored without power-on for a maximum of 90 days. If the
storage period exceeds 90 days, recharge the batteries promptly.
The PAD storage temperature ranges from –20°C to +45°C.
FusionDC1000A Prefabricated All-in-One Data
Center
Product Description (IT Scenario)
2 Typical Application Scenarios and Typical
Conguration
Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd. 9