3.6.6 Cabinet Base
1100 mm deep cabinets and 1200 mm deep cabinets are xed.
A cabinet base has the following features:
Cabinets are raised for 250 mm high and secured to bases, which are
anchored to the steel oor using self-drilling tapping screws.
Cabinet bases can be used for cabinets that are 1100 mm and 1200 mm deep.
The bases can be 1100 mm or 1200 mm deep.
Figure 3-11 Cabinet base
(1) Transport protection
materials
(2) Bottom sealing plate (3) Positioning fastener
3.7 External Ports of the Pre-fab. Module
End connectors are used at the ports designed for routing power cables, optical
bers, and network cables on the pre-fab. module exterior. All ports provide good
water tightness and thermal insulation performance, meeting equipment
compartment weather-tight requirements. Pipe feature an anti-backow design,
adapting to dierent conguration demands. Fire extinguishing devices on the
pre-fab. module exterior meet sealing conditions.