current equalization and intelligent voltage equalization. Old and new battery
strings can be used together, ensuring reliable system operation.
● Implements intra-cabinet and inter-cabinet communication, collects sampling
signals from battery modules, and collects voltage and current signals from
the battery cabinet.
● Protects against exceptions such as overvoltage, undervoltage, overcurrent,
overtemperature, undertemperature, and leakage current in the battery
cabinet.
Only the BCU with the BOM number 02313PYT-001 supports online leakage current
detection.
Figure 4-17 BCU
(1) Positioning lock
(2) Power switch (3) Running indicator (4) Alarm indicator
(5) Fault indicator (6) Ready switch (7) Output ports (8) Input ports
Table 4-12 Indicator description
Indicator
Status Description
Running
indicator
(green)
Steady on Discharging state. The SmartLi circuit
breaker is switched on. In this case, the
UPS can be cold started.
Blinking at intervals of
5s (on for 1s and o for
4s)
Standby state. The SmartLi circuit
breaker cannot be switched on.
Blinking at intervals of
2s (on for 1s and o for
1s)
Charging state. The SmartLi circuit
breaker is switched on. In this case, the
UPS can be cold started.
Blinking at intervals of
0.5s (on for 0.25s and
o for 0.25s)
● The power button is pressed down.
● An upgrade is in progress.
FusionDC1000A Prefabricated All-in-One Data
Center
Product Description (IT Scenario) 4 Power Supply and Distribution System
Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd. 38