(9) BLINK button (10) Status indicator
Specications
Table 6-23 Technical specications of a smart ETH gateway
Item Specications
Power input PWR_IN D-type power input terminal, for power cascading, input
voltage range: 45–55 V DC
Power
output
● PWR_OUT D-type power output terminal, for power
cascading, output voltage range: 45–55 V DC
● 48V_OUT1 and 48V_OUT2, Phoenix terminal, output voltage
range: 45–55 V DC
FE port Two FE ports, RJ45 terminal with an indicator, 10/100M
communication rate, for the cascading between smart ETH
gateways and the communication with the host
PoE port Four PoE ports, RJ45 terminal with an indicator, 10/100M
communications rate, complying with IEEE802.3at
BLINK
button
If you press the BLINK button, the RUN indicator blinks
intermittently at super short intervals (blinking at super short
intervals for 0.5s and then o for 0.5s) for 10s.
6.5 AC Actuator
The AC actuator is used in a smart module to control the lighting inside the smart
module by receiving commands from the access control system or host, infrared
linkage information (disabled by default), or signals from the light button. It also
provides a charging port for the PAD (AC OUT2).
FusionDC1000A Prefabricated All-in-One Data
Center
Product Description (IT Scenario) 6 Management System
Issue 04 (2023-11-10) Copyright © Huawei Digital Power Technologies Co., Ltd. 83