Item Specications
Altitude 0–4000 m, derated at above 1000 m. For details about derating
data, contact Huawei technical support.
Physical Ports
Table 5-3 Physical ports
Item Specications
Refrigerant liquid pipe Copper pipe; outer diameter: 5/8 inch (15.88 mm); wall thickness:
1.0 mm; pressure withstanding capacity ≥ 4.5 MPa; welded
Refrigerant gas pipe Copper pipe; outer diameter: 3/4 inch (19.05 mm); wall thickness:
1.0 mm; pressure withstanding capacity ≥ 4.5 MPa; welded
Humidier water inlet pipe Reserved port: G 1/2 inch, port with inner threads
Top drainage port Reserved port: BSPP 1/2 inch; thread connection
Bottom drainage port Reserved port: copper pipe with an outer diameter of 5/8 inch. A
hose with the inner diameter of 14 mm is recommended.
Installation Requirements
Table 5-4 Installation requirements
Item
Specications
Room door Width ≥ 1.2 m; height ≥ 2.3 m
Floor
Bearing capacity ≥ 530 kg/m
2
; height of the raised oor ≥ 250 mm
Installation mode Installed on a concrete oor, a base, or an ESD oor
Pipe and cable routing Top or bottom routing
Equivalent length of the
one-way pipe
≤ 100 m
Vertical distance between
the indoor and outdoor
units
If the outdoor unit is placed higher than the indoor unit, the
vertical distance between them should be less than or equal to
30 m.
If the indoor unit is placed higher than the outdoor unit, the
vertical distance between them should be less than or equal to 8
m.
Thermal insulation foam
thickness
≥ 13 mm
FusionDC1000A Prefabricated All-in-One Data
Center
Product Description (IT Scenario) 5 Cooling System
Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd. 55