23
Product Overview
6
Power-On Commissioning
• Power on the LUNA2000 within 24 hours after unpacking. The power-off time cannot exceed
24 hours during maintenance.
• After turning on the battery switch, power on the inverter. For details about how to power on
the inverter, see the quick guide for the corresponding inverter model.
• If no PV module is configured, press the black start button.
Turn on the DC switch on the battery. After the battery is installed and powered on for the first
time, the ring LED blinks for three circles. Observe the battery indicator to check the running
status.
Connecting the Battery Supply
6.1
6.2
Status (Blinking at long
intervals: On
Off for 1s; Blinking at short
Intervals:
for 0.2s and then
Off for 0.2s)
Blinking green
at long
intervals
Blinking green
at long
intervals
Blinking red
at short
intervals
Battery power control module environment alarm
Blinking red at
short intervals
Battery expansion module environment alarm
Battery power control module fault
Battery expansion module fault
Battery
system
indication
Indicates battery level. One bar represents 10%.
The first three bars indicate the number of faulty
battery expansion modules.
Downloading the App
Method 1: Search for FusionSolar on Huawei AppGallery and download the latest installation
package.
Method 2: Access https://solar.huawei.com using the mobile phone browser and download the
latest installation package.