A.2.1 Preparations and WebUI Login
Prerequisites
The operating system of Windows 7 or later is supported.
Browser: Chrome 52, Firefox 58, or Internet Explorer 9, or a later version is
recommended.
Procedure
Step 1 Connect the network cable between the network port of the PC and the WAN or
LAN port of the CMU.
Step 2 Set the IP address for the PC on the same network segment as the CMU IP
address.
When the CMU is connected to the SACU
Connected
Port
Item CMU Default
Value
Example PC
Setting
LAN port IP address 192.168.8.10 192.168.8.11
Subnet mask 255.255.255.0 255.255.255.0
Default gateway 192.168.8.1 192.168.8.1
WAN port IP address 192.168.0.10 192.168.0.11
Subnet mask 255.255.255.0 255.255.255.0
Default gateway 192.168.0.1 192.168.0.1
When the CMU is not connected to the SACU
SACU LAN Port IP
Address
CMU WAN Port IP
Address
CMU LAN Port IP
Address
192.168.8.10 192.168.8.XXX 192.168.3.10
XXX.XXX.XXX.XXX
a
XXX.XXX.XXX.XXX
a
192.168.8.10
Note a: When you set the IP address of the SACU LAN port, the IP address
of the CMU WAN port changes with the IP address of the SACU LAN port.
You can view the IP address on the SACU WebUI or SUN2000 app.
Step 3 Set LAN parameters.
NO TICE
If the CMU is connected to a local area network (LAN) and a proxy server has
been set, you need to cancel the proxy server settings.
If the CMU is connected to the Internet and the PC is connected to the LAN, do
not cancel the proxy server settings.
LUNA2000-2.0MWH Series Smart String ESS