NO TE
The cable colors shown in the electrical connection diagrams provided in this section are for
reference only. Select cables in accordance with local cable specications (green-and-yellow
cables are only used for protective earthing). The factors that aect cable selection include
the rated current, cable type, routing mode, ambient temperature, and maximum expected
line loss.
5.2 Preparing Cables
Table 5-1 Cable description (S indicates the conductor cross-sectional area of the AC cable, and S
p
indicates the conductor cross-sectional area of the PE cable)
Cable Type Conductor Cross-
Sectional Area
Outer
Diameter
Source
DC power
cable
(multi-
core)
Two-core outdoor cable and
M12 OT/DT terminal
70–185 mm
2
30–60 mm Prepared
by the
customer
(In the
DCBOX
scenario,
the DC
cables are
preinstalle
d on the
DCBOX
and do
not need
to be
prepared.)
DC power
cable
(single-
core)
Single-core outdoor cable and
M12 OT/DT terminal
50–185 mm
2
15–35 mm
PE cable
[1]
Single-core outdoor copper
cable and M10 OT/DT terminal
S
p
≥ S/2 - Prepared
by the
customer
Communic
ations
cable
FE: CAT 5E outdoor shielded
network cable (internal
resistance ≤ 1 ohm/10 m) and
the shielded RJ45 connector
0.2 mm
2
4.5–7.5 mm 1.2 m,
delivere
d with
the
device
You can
also
prepare
a cable
accordi
ng to
site
require
ments.
LUNA2000-200KTL-H1 Smart Power Control System
User Manual 5 Cable Connection
Issue 08 (2024-01-23) Copyright © Huawei Technologies Co., Ltd. 45