Table 8-1 Maintenance checklist
Check Item Check Method Maintenance
Interval
Cleanness of
the air intake
vent
Cleanness of
the air exhaust
vent
Fan
Check whether there is dust on
the air intake and exhaust vents.
If necessary, remove and clean
the bae plates.
Check whether the fans
generate abnormal noise during
operation.
Once every 6 to 12
months
System status Check whether the enclosure is
damaged or deformed.
Check whether the device
generates abnormal sounds
during operation.
Check whether the parameters
are correctly set during
operation.
Once every 6 months
Cable connection Check whether cables are
disconnected or loose.
Check whether cables are
damaged, especially whether
the cable sheath that contacts a
metal surface is damaged.
Check whether the unused
COM, USB, and FE ports are
locked by waterproof caps.
6 months after the
rst commissioning
and once every 6 to
12 months after that
Grounding
reliability
Check whether the ground cables
are securely grounded.
6 months after the
rst commissioning
and once every 6 to
12 months after that
Removing the Bae Plate from the Air Intake Vent
Figure 8-1 Removing the bae plate
LUNA2000-200KTL-H1 Smart Power Control System
User Manual 8 Device Maintenance