Step 2 Send a shutdown command on the SUN2000 app, SmartLogger, or management
system.
Step 3 Turn o the AC switch between the Smart PCS and the power grid or load.
Step 4 Open the AC maintenance compartment door, install a support bar, and use a
multimeter to check the voltage between the AC terminal block and the ground.
Ensure that the AC side of the Smart PCS is powered o.
Step 5 Turn o the DC switch between the Smart PCS and the DC LV Panel busbar.
Step 6 Open the DC maintenance compartment door, install a support bar, and use a
multimeter to check the voltage between DC terminal blocks. Ensure that the DC
side of the Smart PCS is powered o.
Step 7 Wait for 15 minutes and troubleshoot or repair the Smart PCS.
Figure 8-3 Power-o for maintenance
WARNING
Do not open the panel for maintenance if the Smart PCS is emitting abnormal
smell or smoke, or has obvious exceptions.
If the Smart PCS does not emit abnormal smell or smoke and is intact, repair or
restart it based on the alarm handling suggestions.
----End
8.3 Alarm Reference
For details about alarms, see the LUNA2000-100KTL and 200KTL Series Smart
Power Control System Alarm Reference.
LUNA2000-200KTL-H1 Smart Power Control System
User Manual 8 Device Maintenance
Issue 08 (2024-01-23) Copyright © Huawei Technologies Co., Ltd. 72