Parameter Description
Device Type Set this parameter to IMD.
Port number The IMD uses RS485
communication. Set the COM port
connected to the IMD based on site
requirements.
Address Set the IMD communications
address based on site requirements.
Device model DOLD RN5897.12/011
2. Check whether the quantity of devices connected to the SmartLogger is
correct.
If not all devices are connected, check and ensure that the cascading cables
between devices, the connection positions of the communications cables
between devices and the SmartLogger, and the indicator status are normal.
Then click Auto. Search.
3. Check whether Device status of each device is normal.
– For the on/o-grid PV+ESS system: During initial connection, Device
status of the PCS is yellow, and Device status of the ESS is green.
– For the o-grid PV+ESS system: The UPS auxiliary power supply must be
connected. Device status of the ESS is green (the CMU is green and the
ESU is gray under Monitoring). After the topology is identied, the PCS is
connected and its Device status is gray.
4. Click Monitoring and choose ESS > ESU > ESR > Running Param.. The
quantity of ESMs displayed are the same as the actual quantity of battery
packs connected and the ESM indicators are not red.
– If the quantity of ESMs is incorrect:
Table 4-3 Setting the quantity of battery packs
ESS
Quantity of Battery Packs
LUNA2000-97KWH-1H1 6
LUNA2000-129KWH-2H1 8
LUNA2000-161KWH-2H1 10
LUNA2000-200KWH-2H1 12
a. Check whether the communications cables to the battery packs are
correctly and securely connected.
b. Delete invalid modules under Running Param. on the ESU page. Then,
choose Maintenance > Device Mgmt. > Connect Device and click Auto.
Search.
Commercial and Industrial Microgrid Energy Storage
Solution
Quick Guide (With Third-Party Microgrid Central
Controller) 4 System Power-On and Commissioning