Figure 4-7 Parameter settings after device search
Parameter Description
Scenario under Arrays Operation
Scenario
● In the on-grid scenario, set this
parameter to On-grid.
● In the o-grid scenario, set this
parameter to O-grid.
● In the on/o-grid switchover
scenario, set this parameter to On/
O-grid.
Grid Code Set the grid code of the country or
region where the devices are used.
Working mode under Parameter
Conguration
● In the on-grid scenario, set this
parameter to PQ.
● In the o-grid scenario, set this
parameter to VSG.
Microgrid compatibility under
Parameter Conguration
● In the on-grid scenario, set this
parameter to Disable.
● In the o-grid scenario, set this
parameter to Enable.
Active Power Baseline (kW) under
Parameter Conguration
You are advised to retain the default
value.
Apparent Power Baseline (kVA)
under Parameter Conguration
You are advised to retain the default
value.
Maximum Overload Active Power
(kW) under Parameter Conguration
You are advised to retain the default
value.
Commercial and Industrial Microgrid Energy Storage
Solution
Quick Guide (With Third-Party Microgrid Central
Controller) 4 System Power-On and Commissioning
Issue 04 (2023-12-18) Copyright © Huawei Digital Power Technologies Co., Ltd. 30