– During the process of Search for Device, do not perform upgrade operations (such
as upgrading through the app, management system, or WebUI).
– When you click Search for Device, cable connections (DC and AC) will be checked
before device search (not applicable to third-party devices), and device addresses
will be automatically allocated.
– After the cable connection check and device search are complete, if a cable
connection alarm is generated, you can click the alarm icon
to view the
corresponding alarm information.
– If an alarm is generated when the cable connection check fails, click the alarm icon
to view the alarm cause and handling suggestions. After the fault is rectied,
check the cable connection again.
– After the cable connection check and device search are complete, click to view
the corresponding topology information.
– After a device is added or deleted, you need to click Search for Device again.
Otherwise, the system topology will not be updated.
3. Connect to a power meter, and set Meter usage to Export+import meter.
Figure 10-14 Setting meter parameters
4. Connect to EMIs.
Figure 10-15 Setting EMI parameters
LUNA2000-200KWH-2H1 Smart String ESS
User Manual 10 SmartLogger Web-based Deployment
Issue 03 (2023-03-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 135