– The working mode is set to Maximum self-consumption.
Figure 10-17 Working mode
Parameter Description
Active power
threshold of
grid during
battery
discharge
Control the maximum target grid power when the
grid-connection point has zero power.
Adjustment
deadband
Allowed uctuation of the target grid power for the
grid-connection point
Automatic
SOC
calibration
▪ Enable: Automatic SOC calibration is enabled. If the
total charge and discharge energy reaches the
threshold or the calibration function has not been
triggered for 30 days, the SOC automatic calibration
is performed. The SOC automatic calibration is
performed in battery racks. During calibration, the
cut-o SOC settings will be ineective.
▪ Disable: Automatic SOC calibration is disabled.
– The working mode is set to TOU.
Figure 10-18 Working mode
LUNA2000-200KWH-2H1 Smart String ESS
User Manual 10 SmartLogger Web-based Deployment
Issue 03 (2023-03-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 138