Procedure
Step 1 Choose Settings > Battery Control > Capacity Limit to set the capacity limit.
Figure 10-25 Setting capacity limit
Parameter Description
No control If this parameter is set to No control, the capacity of the grid-
connection point is not limited. The inverter and Smart PCS run
according to the preset control policy.
Active
capacity limit
If this parameter is set to Active capacity limit, the active
power of the grid-connection point for purchasing or feeding
power cannot exceed the preset capacity limit.
Apparent
capacity limit
If this parameter is set to Apparent capacity limit, the apparent
power of the grid-connection point for purchasing or feeding
power cannot exceed the preset capacity limit.
----End
Active Capacity Limit
Parameter
Description
Maximum
active
capacity
Set this parameter according to the charging capacity in the
demand contract of the power grid company. Once set, the
active power of the grid-connection point for purchasing or
feeding power cannot exceed the preset value.
PV power
limit when
electricity
meter fails
Species the active power limit of the inverter when the feed-in
meter communication is abnormal. You can manually change
the active power percentage of the inverter as required.
PCS power
limit when
electricity
meter fails
Species the active power limit of the PCS when the feed-in
meter communication is abnormal. You can manually change
the active power percentage of the PCS as required.
LUNA2000-200KWH-2H1 Smart String ESS
User Manual 10 SmartLogger Web-based Deployment
Issue 03 (2023-03-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 143