4. If a lithium battery is stored for a long time, capacity loss may occur. After a
lithium battery is stored for 12 months in the recommended storage
temperature, the irreversible capacity loss rate is 3%–10%. If customers
perform the discharge test according to the specications, they may fail to
pass the test if the storage capacity of the battery is not 100% of the rated
capacity.
Inspection Before Recharge
1. Before recharging a battery, you need to check its appearance. Recharge the
battery if it is qualied or dispose of it if not.
2. The battery is qualied if it is free from the following symptoms:
– Deformation
– Shell damage
– Leakage
Battery Recharging Scenarios
indicates a power cable, indicates a signal cable, indicates
wireless communication.
Three-Phase Power Supply Scenario
● The SUN2000-10KTL-M1 provides 10 kW power to charge batteries. It allows
two charge units (four battery packs) to be charged at the same time. For
other inverter models, see the following tables.
Figure 8-1 Networking diagram for three-phase power supply scenario
(C) SUN2000-10KTL-M1
(D) AC switch (E) ACDU
(G) Power grid (H) LUNA2000 (M) FusionSolar app
LUNA2000-(5-30)-S0
User Manual 8 System Maintenance
Issue 15 (2024-01-12) Copyright © Huawei Digital Power Technologies Co., Ltd. 131