No. Cable Type Source
3 Ground cable Single-core outdoor copper cable Delivered
with the
product
● indicates a power cable, indicates a signal cable, indicates
wireless communication, indicates a ground cable.
● The minimum cable diameter must comply with local cable standards.
● The factors that aect cable selection include the rated current, cable type, routing
mode, ambient temperature, and maximum expected line loss.
● The DC input power cable and signal cable between the battery and the inverter must
be less than or equal to 10 m.
6.2 Internal Electrical Connections of the Battery
Internal cables are delivered with the battery. For details, see the
Packing List
in the packing
case.
6.2.1 Installing an Internal Ground Cable
Precautions
Ensure that the PE cable is securely connected. Otherwise, electric shocks may
occur.
It is recommended that silica gel or paint be used around the ground terminal after the PE
cable is connected.
Step 1 Connect the PE cable to the battery power control modules and battery expansion
modules.
LUNA2000-(5-30)-S0
User Manual 6 Electrical Connection
Issue 15 (2024-01-12) Copyright © Huawei Digital Power Technologies Co., Ltd. 80