Figure 10-2 Security risk warning
2. Select a desired language.
3. Select User Name and enter Password according to the following table, and
then click Log In.
If... Then...
On the login page,
User Name is
admin by default.
1. Enter the initial password Changeme in
Password and click Log In.
2. Change the initial password as prompted and use
the admin user name and new password to log in
again.
On the login page,
User Name is
empty by default.
Select installer in User Name, set the login
password as prompted, and click Log In.
NO TE
Update the SmartLogger software as required.
To ensure account security, protect the password by changing it periodically, and
keep it secure. Your password might be stolen or cracked if it is left unchanged for
extended periods. If you lose the password, the device must be restored to its
factory settings. In these cases, the Company shall not be liable for any loss caused
to the plant.
You will be locked out for 10 minutes after ve consecutive failed password
attempts in 5 minutes.
A dialog box with recent login information is displayed after login. Click OK.
If the password of a non-administrator account is lost, you must reset the
password using an administrator account. The administrator resets the password
and enters the initial password. The non-administrator user logs in to the system
using the initial password provided by the administrator. After the login, the user is
forced to change the password.
If the password of an administrator account is lost, hold down the RST button on
the SmartLogger for 10–20s to enter the safe mode. After the SmartLogger enters
the safe mode, the device parameter settings are retained. Personal privacy and
sensitive data, including login passwords and email addresses, will be deleted.
SmartLogger V300R023C00 and later versions support this function.
4. Choose Monitoring > Logger(Local) > About to view the SmartLogger
software version and check whether software upgrade is needed.
LUNA2000-(97KWH-1H1, 129KWH-2H1,
161KWH-2H1, 200KWH-2H1) Smart String ESS
User Manual 10 Commissioning the ESS (SmartLogger WebUI)
Issue 10 (2023-11-07) Copyright © Huawei Digital Power Technologies Co., Ltd. 136