Figure 10-7 Checking the ESM software version
● If the software version of an ESM is not the latest version in FusionSolar Software
Download, upgrade the ESS and ensure that the ESM software version matches the
SmartLogger software version.
● If an alarm Version Inconsistent Between Rack Controller and Battery Packs or
Version Incompatible Between Rack Controller and Battery Packs is generated,
upgrade the ESS.
● Obtain the upgrade package from the Company.
Step 5 Choose Maintenance > Software Upgrade, upload the upgrade package, select
the CMU, CMU_BSP, and ESU, and upgrade the software.
Figure 10-8 Upgrading the ESU
Step 6 Choose Monitoring > ESM and check in the upper right corner to ensure that
no major alarm is generated.
----End
10.5 System Startup
Context
Start up the system when needed.
Procedure
Step 1 On the SmartLogger WebUI, choose Maintenance > Device Mgmt. > Connect
Device.
LUNA2000-(97KWH-1H1, 129KWH-2H1,
161KWH-2H1, 200KWH-2H1) Smart String ESS
User Manual 10 Commissioning the ESS (SmartLogger WebUI)
Issue 10 (2023-11-07) Copyright © Huawei Digital Power Technologies Co., Ltd. 140