Procedure
Step 1 Choose Monitoring > ESS > CMU on the SmartLogger WebUI.
Step 2 Choose Running Param. > Door Status Alarm to set Burglar Alarm.
Param
eter
Setting Description
Burglar
Alarm
Disable No burglar alarm will be triggered when the ESS door is
open.
Enable A burglar alarm will be triggered when the ESS door is
open.
----End
10.9 Setting Capacity Limit
Context
● Time-of-use (TOU) with capacity limit:
When the capacity limit is enabled in TOU mode, the charge/discharge time
set in the TOU window must cover 24 hours a day. Capacity limit is not
supported in non-charge/discharge time.
● Capacity limit:
– If the capacity limit is met 24 hours a day, the ratio of the ESS/PCS to the
load power must be properly set to ensure that the ESS/PCS have
sucient capacity to meet the capacity limit.
– When the ESS is used only for capacity limit, you can set the charge time
to 24 hours in the TOU window. Do not set the discharge time and non-
charge/discharge time.
– The overload capability of transformers, power distribution switches, and
cables must be greater than the sum of the maximum charge current and
maximum load current of the ESS.
Procedure
Step 1 Choose Settings > Battery Control > Capacity Limit to set the capacity limit.
Figure 10-18 Setting capacity limit
LUNA2000-(97KWH-1H1, 129KWH-2H1,
161KWH-2H1, 200KWH-2H1) Smart String ESS
User Manual 10 Commissioning the ESS (SmartLogger WebUI)
Issue 10 (2023-11-07) Copyright © Huawei Digital Power Technologies Co., Ltd. 155