Technical Specications Rack Controller
Surge protection Supported (bus side)
Insulation resistance detection Supported
Overtemperature protection Supported
Overcurrent protection on the battery
side
Supported
Short circuit protection on the battery
side
Supported
Short circuit protection on the bus side Supported
Table 2-10 General specications
Technical Specications Rack Controller
Parallel mode Two rack controllers connected in
parallel on the battery side and two on
the bus side
Power overload Long-term running at 1.1 times the
rated power
Overvoltage category Bus side DC II
Dimensions (H x W x D) 270 mm x 600 mm x 820 mm
Weight ≤ 90 kg
DC surge protection on the bus side Type II
Operating temperature range –30°C to +60°C (The rack controller
can be started at –40°C.)
Operating humidity range 0%~100%
Storage temperature –40°C to +70°C
Storage humidity 5%–95% RH
Cooling mode Smart air cooling
IP rating IP66
Maximum operating altitude 4000 m
Input and output terminals OT terminals
Power response time (from no load to
full load)
< 30 ms
LUNA2000-(97KWH-1H1, 129KWH-2H1,
161KWH-2H1, 200KWH-2H1) Smart String ESS
User Manual 2 Product Description
Issue 10 (2023-11-07) Copyright © Huawei Digital Power Technologies Co., Ltd. 33