Figure 6-47 Running/Alarm indicator on a power module
Step 10 Conrm the replacement.
After the preceding procedure is complete, check services on the host for storage-
related errors. If any storage-related error is reported, contact Huawei technical
support.
----End
Follow-up Procedure
After the power module is replaced, label it to facilitate subsequent operations.
6.2.5 Replacing a Power Module (Disk Enclosure)
This section describes how to replace a power module. Except that there is a slight
dierence on removing and inserting power cables between AC and DC power
modules, other operations performed for them are the same. This section uses AC
power modules as an example.
Impact on the System
During the replacement of a power module, if the redundant power module fails,
the corresponding disk enclosures are unexpectedly powered
o, causing all
services in the disk enclosures to be interrupted.
Prerequisites
● The spare part is on hand.
● The power module that you want to replace has been located.
You can locate a component in either of the following ways:
● Locating a component based on alarms in DeviceManager: On the Alarms and Events
page of DeviceManager, view the help information and determine the ID of the
component to be replaced. Then locate the component at your site based on its ID.
● Locating a component based on the status of its Running/Alarm indicator: For details
about the indicators on
dierent components, see Indicator Introduction of each
component in the
Product Description
specic to your product model and version.
Precautions
● Do not touch the connectors of a power module and a power cable.
● Remove and insert a power module with even force. Excessive force may
damage the appearance or connectors of the power module.
OceanStor V5 Series
Parts Replacement 6 Replacing CRUs
Issue 15 (2019-12-30) Copyright © Huawei Technologies Co., Ltd. 56