Step 10 Conrm the replacement.
After the preceding procedure is complete, check services on the host for storage-
related errors. If any storage-related error is reported, contact Huawei technical
support.
----End
Follow-up Procedure
After the BBU is replaced, label it to facilitate subsequent operations.
6.3.2 Replacing a BBU (for 5600 V5/5800 V5/5600F V5/5800F
V5)
This section describes how to replace a BBU.
Impact on the System
● Replacing a BBU
aects data security.
● During the replacement, if all other BBUs fail, the system is no longer BBU-
protected. To enhance data security, the system forcibly implements LUN
write through, and the system performance is compromised.
Prerequisites
● The spare part is on hand.
●
Conguration data has been backed up.
● The BBU that you want to replace has been located.
You can locate a component in either of the following ways:
● Locating a component based on alarms in DeviceManager: On the Alarms and Events
page of DeviceManager, view the help information and determine the ID of the
component to be replaced. Then locate the component at your site based on its ID.
● Locating a component based on the status of its Running/Alarm indicator: For details
about the indicators on
dierent components, see Indicator Introduction of each
component in the
Product Description
specic to your product model and version.
Precautions
● Remove and insert a BBU with even force. Excessive force may damage the
appearance or connectors of the BBU.
● Remove only one BBU at a time.
● When a BBU is being replaced, the storage system does not have BBU
redundancy. Therefore, you are advised to replace a BBU as quickly as
possible.
● A BBU must be replaced within
ve minutes. Otherwise, the system heat
dissipation is compromised.
OceanStor V5 Series
Parts Replacement 6 Replacing CRUs
Issue 15 (2019-12-30) Copyright © Huawei Technologies Co., Ltd. 72