Figure 6-1 Cable ties without sharp burs
Figure 6-2 Cable ties in the same direction
Figure 6-3 Binding cables in dierent colors
Table 6-2 Cable bundle binding intervals
Cable Bundle Diameter (mm)
Binding Interval (mm)
< 10 150
10–30 200
> 30 300
Bending Cables
Table 6-3 Bending rules
No.
Bending Rule
1 Cables should not be overly bent as over-bending may damage
the cable cores.
2 Unless otherwise stipulated, the bending radius should be 10
times greater than the cable diameter if the installation space is
sucient.
3 Cables should not be tied where they bend, as shown in Figure
6-4.
PDU8000 DC Combiner Cabinet
Quick Guide 6 Installing Cables