● The MDU is not restarted if the software for the monitoring board is activated and is
restarted if the software for the MDU is activated.
● If the PDC is powered
o when the software for the monitoring board is being
upgraded, the information about the monitoring board is not displayed after the MDU is
restarted. In this case, tap Upgrade Software to continue the upgrading process. If the
PDC is powered
o when the software for the MDU is being upgraded, perform the
upgrading again after the MDU is restarted.
● After the software is upgraded, the MDU parameters remain unchanged and do not
need to be reset.
----End
7.4.4.2 Loading Congurations
Context
The Load Cong. function enables you to set system parameters.
Note that the function may change the original model conguration parameter
values. Exercise caution when using this function.
Procedure
Step 1 Connect a USB ash drive to the USB Host port.
Figure 7-50 Inserting the USB ash drive
PDU8000 Modular Precision PDC V2.0
User Manual 7 MDU Commissioning Guide