Figure 5-32 Connecting the equipotential ground cables for the cabinet
Step 4 Connect the input power cables.
● In single-input scenarios, connect the input N cable to 1N.
● When connecting the input power cables, verify that the screw assemblies face
the same direction, and that the nuts face the cabinet rear door.
● Connect the three-phase cables, N cable, and PE cable in sequence.
Figure 5-33 Connecting input power cables
Step 5 Connect the output power cables.
PDU8000 Modular Precision PDC V2.0
User Manual 5 Installation Guide
Issue 04 (2021-04-13) Copyright © Huawei Technologies Co., Ltd. 56