Figure 4-5 Securing a charging module (horizontal mounting)
Figure 4-6 Securing a charging module (side mounting)
----End
4.4 Connecting Cables
4.4.1 Connecting DC Output Power Cables
● The metal socket is delivered with the DC output connector.
● Check whether the metal socket is reliably crimped. The minimum pull-out
force is 500 N for 6 AWG cables or cables with a cross-sectional area of 16
mm
2
.
● The front end of the heat-shrink tubing should not exceed the scale on the
metal socket. The outer diameter of the metal wire covered with the heat-
shrink tubing is less than or equal to 9.1 mm.