5 Powering On the Charging Module and
Setting Parameters
● After the installation is complete, power on the charging module. Use a
multimeter to check whether the voltage at the cabinet copper bar connected
to the output connector of the charging module is within the normal range
(200–506 V DC in low-voltage mode and 200–1000 V DC in high-voltage
mode).
● Check that the power indicator on the charging module is steady on and the
voltage displayed on the nixie tubes is the same as that measured by the
multimeter.
● Set the hardware address of the charging module if grouping is required.
R100030G1 Charging Module
User Manual
5 Powering On the Charging Module and Setting
Parameters
Issue 05 (2021-11-16) Copyright © Huawei Digital Power Technologies Co., Ltd. 30