LUNA2000-200KWH-2H1 Smart String ESS
User Manual
6 Alarm Reference
Copyright © Huawei Technologies Co., Ltd.
134
Alarm
ID
Alarm
Name
Severity
Possible Cause
Suggestion
by referring to the product
maintenance manual.
4. After checking that the battery power
cable is correctly connected, turn on
the switch on the battery side and then
the switch on the bus side, and issue a
startup command.
5. If the alarm persists, contact your
dealer or technical support.
3021
Insulation
Resistance
of Rack
Controller
Abnormal
Major
Cause ID = 13
1. The battery is
short-circuited to the
ground.
2. The battery is in a
humid environment
and the insulation
between the battery
and ground is poor.
1. Locate the input and output circuit
breakers associated with [ESC-No].
2. Issue a hibernation command to the
ESR corresponding to the ESC, and turn
off the switch on the battery side and the
switch on the bus side in sequence, and
wait for 5 minutes.
3. Check the ground impedance of the
battery output (measured on both the
battery side and the bus side). If a short
circuit occurs or the insulation is
insufficient, rectify the fault.
4. Check whether the PE cable of the
system is correctly connected.
5. If the impedance is lower than the
specified protection threshold in rainy and
cloudy days, set Insulation resistance
protection threshold using the mobile app,
SmartLogger, or NMS.
6. After checking that the battery power
cable is correctly connected, turn on the
switch on the battery side and the switch
on the bus side in sequence, and issue a
running command.
7. If the alarm persists, contact your
dealer or technical support.
3022
Rack
Controller
Temperatur
e High
Minor
Cause ID = 19
1. The installation
position of the battery
power control module is
not well ventilated.
2. The ambient
temperature is too high.
3. The battery power
control module is
abnormal.
4. The fan of the battery
power control module is
1. Check the ventilation of [ESC-No]
and whether the ambient temperature
of the optimizer exceeds the upper
threshold.
2. If the ventilation is poor or the
ambient temperature exceeds the
upper threshold, improve the
ventilation and heat dissipation.
3. Check whether the internal or external
fan of the rack controller is faulty.
4. If the ventilation and ambient
temperature meet requirements,
contact your dealer or technical

Table of Contents