No. Cable Category Conductor
Cross-Sectional
Area Range
Outer
Diameter
Source
5 AC output
power cable
(multi-core)
If you connect a ground
cable to the ground point
on the device enclosure
and the neutral wire is
not used, you are advised
to use a three-core (L1,
L2, and L3) outdoor
cable and M12 OT/DT
terminals (L1, L2, and
L3).
If you connect a PE cable
to the ground point in
the maintenance
compartment and the
neutral wire is not used,
you are advised to use a
four-core (L1, L2, L3, and
PE) outdoor cable, M12
OT/DT terminals (L1, L2,
and L3), and M10 OT/DT
terminals (PE).
If you connect a ground
cable to the ground point
on the device enclosure
and the neutral wire is
used, you are advised to
use a four-core (L1, L2,
L3, and N) outdoor cable
and M12 OT/DT
terminals (L1, L2, L3, and
N).
If you connect a PE cable
to the ground point in
the maintenance
compartment and the
neutral wire is used, you
are advised to use a
ve-
core (L1, L2, L3, N, and
PE) outdoor cable, M12
OT/DT terminals (L1, L2,
L3, and N), and M10
OT/DT terminals (PE).
Copper
cable:
S: 70–240
mm
2
S
p
≥ S/2
Aluminum
alloy cable
or copper-
clad
aluminum
cable:
S: 95–240
mm
2
S
p
≥ S/2
24–66 mm Prepared
by the
customer
SUN2000-(100KTL, 110KTL, 115KTL)-M2
User Manual 5 Electrical Connections
Issue 07 (2023-04-30) Copyright © Huawei Technologies Co., Ltd. 48