Loading...
SUN2000-(50KTL-JPM0, 50KTL-JPM1, 63KTL-JPM0)
User Manual
7 Man-Machine Interactions
Copyright © Huawei Technologies Co., Ltd.
70
Figure 7-4 Feature parameters (advanced user)
----End
Parameter List
No.
Parameter
Description
Unit
Default
Value
Value Range
Remarks
1
MPPT
multi-peak
scanning
When the SUN2000 is
used in scenarios
where PV strings are
obviously shaded,
enable this function.
Then the SUN2000
will perform MPPT
scanning at regular
intervals to locate the
maximum power.
N/A
Disable
Disable
Enable
The scanning
interval is set by
MPPT multi-peak
scanning interval.
2
MPPT
multi-peak
scanning
interval
Specifies the MPPT
multi-peak scanning
interval.
min
15
[5, 30]
This parameter is
displayed only when
MPPT multi-peak
scanning is set to
Enable.