SUN2000-(50KTL-JPM0, 50KTL-JPM1, 63KTL-JPM0)
User Manual
7 Man-Machine Interactions
Copyright © Huawei Technologies Co., Ltd.
76
No.
Parameter
Description
Unit
Default
Value
Value Range
Remarks
14
Communic
ation
interruptio
n duration
Specifies the duration
for determining
communication
interruption, and is
used for automatic
shutdown for
protection in case of
communication
interruption.
min
30
[1, 120]
N/A
15
Soft start
time
Specifies the duration
for the power to
gradually increase
when the SUN2000
starts.
s
20
[20, 1800]
N/A
16
OVGR
linked
shutdown
If this parameter is set
to Enable, the
SUN2000 shuts down
after receiving the
OVGR signal. If this
parameter is set to
Disable, the
SUN2000 does not
shut down after
receiving the OVGR
signal.
N/A
Enable
Disable
Enable
N/A
17
Dry contact
function
Identifies dry contact
signals sent from the
SmartLogger.
N/A
NC
NC
OVGR
Set this parameter to
OVGR for OVGR
signals, and set it to
NC for other
signals.
18
Hibernate
at night
The SUN2000
monitors PV strings at
night. If Hibernate at
night is set to Enable,
the monitoring
function of the
SUN2000 will
hibernate at night,
reducing power
consumption.
N/A
Disable
Disable
Enable
N/A