does not
affect the
power
supply to
loads.
is installed,
the UPS
shuts down.
The mains voltage exceeds
280 V.
The mains voltage is less
than 80 V.
The mains frequency is not
in the range of 40 Hz to 70
Hz.
The mains fuse is abnormal.
input voltage is less than 272
V. If not, wait until the mains
input voltage is greater than
88 V. If yes, the mains fuse
may be abnormal. Replace
the faulty device. If no, wait
until the mains recovers.
Check the mains input
frequency. If it is abnormal,
wait until the mains input
recovers.
The UPS cannot
transfer to
bypass mode. If
the UPS is
working in
bypass mode, it
transfers to
another
working mode.
The bypass input voltage is
abnormal.
The bypass input frequency
is abnormal.
Check whether the bypass
input voltage exceeds the
configured range. If yes,
change the range or wait
until the bypass input
recovers.
input frequency exceeds the
configured range. If yes,
change the range or wait
until the bypass input
recovers.
For more parameters and alarm information, see
UPS2000-G-(6 kVA-20 kVA) User Manual
.
Typical Alarm Handling