34
Alarm
Name
Alarm ID
-
Cause ID
Alarm
Severity
Clearance
Mode
Impact on the
System
Handling Suggestion
Abnormal
mains volt.
0001
-01
Minor
Automatic
The rectifier
transfers to
battery
mode, which
does not
affect the
power
supply to
loads.
If no battery
is installed,
the UPS
shuts down.
Possible causes:
The mains voltage exceeds
280 V.
The mains voltage is less
than 80 V.
The mains frequency is not
in the range of 40 Hz to 70
Hz.
The mains fuse is abnormal.
Measures:
Check whether the mains
input voltage is less than 272
V. If not, wait until the mains
recovers.
Check whether the mains
input voltage is greater than
88 V. If yes, the mains fuse
may be abnormal. Replace
the faulty device. If no, wait
until the mains recovers.
Check the mains input
frequency. If it is abnormal,
wait until the mains input
recovers.
0001
-02
Minor
0001
-03
Minor
Abnormal
BPS volt.
0010
-01
Minor
Automatic
The UPS cannot
transfer to
bypass mode. If
the UPS is
working in
bypass mode, it
transfers to
another
working mode.
Possible causes:
The bypass input voltage is
abnormal.
The bypass input frequency
is abnormal.
Measures:
Check whether the bypass
input voltage exceeds the
configured range. If yes,
change the range or wait
until the bypass input
recovers.
Check whether the bypass
input frequency exceeds the
configured range. If yes,
change the range or wait
until the bypass input
recovers.
0010
-02
Minor
For more parameters and alarm information, see
UPS2000-G-(6 kVA-20 kVA) User Manual
.