Alarm
Name
Alarm ID
-
Cause ID
Alarm
Severity
Clearance
Mode
Impact on the
System
Handling Suggestion
Mains
phase
reverse
0004
-01
Minor
Automatic
The rectifier
transfers to
battery mode,
which does
not affect the
system power
supply.
If no battery is
installed, the
UPS shuts
down.
The UPS
transfers to
another
working mode
or shuts
down.
Possible cause: The mains input
three
-phase sequence is
incorrect.
Measure: Check that mains
input power cables are correctly
connected.
BPS phase
reverse
0011
-01
Minor
Automatic
If the inverter
has not
started, the
output keeps
disconnected
and the
inverter is not
allowed to
start.
If the inverter
has started,
the UPS can
work in
inverter mode
properly, but
the UPS
cannot
transfer to
bypass mode.
Possible cause: The bypass input
three
-phase sequence is
incorrect.
Measure: Check that bypass
input power cables are correctly
connected.
Batt
.
overvolt
.
0025
-01
Minor
Automatic
An alarm is
displayed, and
the battery
service life may
be shortened.
Possible causes:
The configured number of
batteries is less than the
actual number.
The battery voltage reaches
the alarm threshold due to
continuous charge.
Measures:
Check battery parameter
settings.
Wait for 2 minutes in battery
charging state. Check
whether the alarm is cleared.