Inverter
fault
0060-04 Critical Power-off The UPS
shuts down.
The UPS may
transfer to
another
working
mode or shut
down.
Possible cause: The inverter
output is short
Measure: Rectify output port
short circuits. Power on and
restart the UPS. If the alarm
persists, contact Huawei
technical support.
On
bypass
0158-01 Minor Automatic If the bypass
is abnormal,
the UPS may
power off.
The inverter is not started.
The load power exceeds
the rated inverter loading
capability.
Check whether other
alarms are raised. If other
alarms are raised, clear
them.
If no alarm is raised, start
the UPS manually.
On
battery
0159-01 Minor Automatic The UPS may
power off if
batteries are
abnormal.
The mains input is
abnormal.
The UPS is in battery self-
check state.
The mains loading
capability is insufficient.
Check the mains input. If it
is abnormal, wait until the
mains input recovers.
Check whether the UPS is
in battery self-check state.
Reduce the load or replace
the UPS with a larger-
capacity UPS.
No
battery
0022-01 Minor Automatic This alarm
does not
affect the
power supply.
Batteries are not
connected.
Batteries are not securely
connected.
Check that batteries are
securely connected.