Figure 5-1 AC input, output, and battery wiring diagram
5.2.1.1 Starting the UPS Using Mains Power
Procedure
Step 1 Switch on the external battery circuit breaker (if any).
Step 2 Switch on the external AC input circuit breaker K
m
for the UPS. The UPS will enter
bypass mode.
Figure 5-2 Bypass mode
Step 3 Press and hold SELECT for 1s on a non-setting screen to access the login screen for
parameter settings. The initial password is 000001. Enter the correct password to
access the UPS setting mode.
UPS2000-G-6KRTLL
User Manual 5 Operations
Issue 02 (2022-06-30) Copyright © Huawei Technologies Co., Ltd. 94