Figure 5-5 Standby mode
Step 3 Press and hold SELECT for 1s on a non-setting screen to access the login screen for
parameter settings. The initial password is 000001. Enter the correct password to
access the UPS setting mode.
Step 4 Set the output voltage based on site requirements.
Output Voltage Description
220: The output voltage is 220 V AC.
230: The output voltage is 230 V AC
(default).
240: The output voltage is 240 V AC.
Step 5 Set the battery capacity.
Battery Capacity
Description
● Default value: 100 Ah
● Value range: 50–2400 Ah. The value
is incremented by 50 Ah each time
you press SELECT.
● When setting the battery capacity,
set the capacity of the battery
string connected to the UPS.
Step 6 Press and hold ON/MUTE for more than 5s. Release the button when you hear a
beep sound. The UPS starts to work in battery mode.
UPS2000-G-6KRTLL
User Manual 5 Operations
Issue 02 (2022-06-30) Copyright © Huawei Technologies Co., Ltd. 97