Item Specications
Bypass voltage
range
176–280 V AC
Bypass frequency 50 Hz/60 Hz
Input frequency
range
50 Hz/60 Hz±4 Hz (When the input frequency exceeds the
synchronization range, the output power is derated to
80%.)
Bypass overload
capability
Load < 125%: continuous working
125% ≤ Load < 150%: Disconnect the output after 1
minute.
150% ≤ Load: Disconnect the output after 100 ms.
Load = Output current/Rated output current
Transient
withstand current
10 kA
Input mode The mains input and bypass input share a power source.
7.5 Output Electrical Specications
Table 7-5 Output electrical specications
Item
Specications
Rated capacity 6 kVA/5.4 kW
Output power factor 0.9
Rated output voltage 220 V AC/230 V AC/240 V AC
Output voltage precision ±1%
Output frequency When the mains is normal, the UPS
automatically tracks the mains frequency.
When the mains is abnormal, the output
frequency is 50 Hz/60 Hz (tolerance ±0.5%).
System eciency Maximum eciency: ≥ 93%
100% resistive load: ≥ 92%; 50% resistive
load: ≥ 93%; 30% resistive load: ≥ 91%
Waveform (battery mode) Sine wave
THDv < 5% (non-resistive loads)
< 3% (resistive loads)
UPS2000-G-6KRTLL
User Manual 7 Technical Specications
Issue 02 (2022-06-30) Copyright © Huawei Technologies Co., Ltd. 112