Name Display Description
Automatically
return to the
default screen
Return to the default
screen (default): If no
button is pressed within
1 minute in any mode,
the default screen
(input voltage/output
voltage) is displayed.
Stay on the current
screen: The currently
opened screen is
displayed.
Equalized charge
voltage
Default value: 54.0 V
When the lithium
battery
communication is
unavailable, the
value range is 53.5–
57.0 V. The value is
incremented by 0.1 V
each time you press
SELECT.
When the lithium
battery
communication is
available, the UPS
automatically adapts
to the equalized
charge voltage based
on the connected
lithium battery
model. The value is
xed and cannot be
changed.
UPS2000-G-6KRTLL
User Manual 4 Control Panel