Alarm ID Alarm
Name
Severity Clearance
Condition
Trigger
Condition
Impact on
the System
Suggestion
20 Lithium
battery
high
temperatur
e protection
Minor The cell
temperatur
e drops
below the
protection
threshold.
Charge
high
temperat
ure
protectio
n: The
maximu
m cell
temperat
ure is
greater
than
60°C.
Discharg
e high
temperat
ure
protectio
n: The
maximu
m cell
temperat
ure is
greater
than
65°C.
The
internal
switch
circuit of
the
lithium
battery
is
disconne
cted,
and the
battery
cannot
be
charged
or
discharg
ed.
The ALM
indicator
on the
faulty
lithium
battery
turns
red.
Possible
cause: The
ambient
temperatur
e of the
lithium
battery is
too high or
there are
abnormal
heat
sources
around the
lithium
battery.
Measure: If
the lithium
battery
cannot be
recovered
due to
protection
against
abnormality
, contact
local
Huawei
engineers
to rectify
the fault.
UPS2000-G-6KRTLL
User Manual 4 Control Panel